< BACK TO DSE

The following chart below is from both electrical industry standards; it matches NEMA Ratings with its IP counterpart, with a brief description of each rating.


Download as a PDF
NEMA
Rating
IP
Equivalent
NEMA Definition IP Against
Objects
IP Against
Liquids
1
IP10
Enclosures constructed for indoor use; to provide a degree of protection to personnel against incidental contact with the enclosed equipment and to provide a degree of protection against falling dirt
1 = Protected against solid foreign objects of 5 cm (2 in) in diameter and greater
0 = Not protected
2
IP11
Enclosures constructed for indoor use; to provide a degree of protection to personnel against incidental contact with the enclosed equipment; to provide a degree of protection against falling dirt, and to provide a degree of protection against dripping and light splashing of liquids
1 = Protected against solid foreign objects of 5 cm (2 in) in diameter and greater
1 = Protected against vertically falling water drops
3
IP54
Enclosures constructed for indoor or outdoor use; to provide a degree of protection to personnel against incidental contact with the enclosed equipment; to provide a degree of protection against falling dirt, rain, sleet, snow and windblown dust; and that will be undamaged by external formation of ice on the enclosure
5 = Protected against dust; limited to ingress (no harmful deposit)
4 = Protected against water sprayed from all directions; limited to ingress permitted
3R
IP14
Enclosures constructed for indoor or outdoor use; to provide a degree of protection to personnel against incidental contact with the enclosed equipment; to provide a degree of protection against falling dirt, rain, sleet and snow; and that will be undamaged by external formation of ice on the enclosure
1 = Protected against solid foreign objects of 5 cm (2 in) in diameter and greater
4 = Protected against water sprayed from all directions; limited to ingress permitted
3S
IP54
Enclosures constructed for indoor or outdoor use; to provide a degree of protection to personnel against incidental contact with the enclosed equipment; to provide a degree of protection against falling dirt, rain, sleet, snow and windblown dust; and in which the external mechanism(s) remain operable when ice laden
5 = Protected against dust; limited to ingress (no harmful deposit)
4 = Protected against water sprayed from all directions; limited to ingress permitted
4
IP56
Enclosures constructed for indoor or outdoor use; to provide a degree of protection to personnel against incidental contact with the enclosed equipment; to provide a degree of protection against falling dirt, rain, sleet, snow, windblown dust, splashing water and hose-directed water; and that will be undamaged by external formation of ice on the enclosure
5 = Protected against dust; limited to ingress (no harmful deposit)
6 = Protected against strong jets of water from all directions; limited to ingree permitted
4X
IP56
Enclosures constructed for indoor or outdoor use; to provide a degree of protection to personnel against incidental contact with the enclosed equipment; to provide a degree of protection against falling dirt, rain, sleet, snow, windblown dust, splashing water and hose-directed water, and corrosion; and that will be undamaged by external formation of ice on the enclosure
5 = Protected against dust; limited to ingress (no harmful deposit)
6 = Protected against strong jets of water from all directions; limited to ingree permitted
5
IP52
Enclosures constructed for indoor use; to provide a degree of protection to personnel against incidental contact with the enclosed equipment; to provide a degree of protection against falling dirt; against settling airborne dust, lint, fibers and flyings: and to provide a degree of protection against dripping and light splashing of liquids
5 = Protected against dust; limited to ingress (no harmful deposit)
2 = Protected against direct sprays of water up to 15° from the vertical
6
IP67
Enclosures constructed for indoor or outdoor use; to provide a degree of protection to personnel against incidental contact with the enclosed equipment; to provide a degree of protection against falling dirt; against hose-directed water and the entry of water during ocassional temporary submersion at a limited depth; and that will be undamaged by external formation of ice on the enclosure
6 = Totally protected against entry of dust
7 = Protected against effects of submersion from 15 cm (6 in) to 1 m (3 ft)
6P
IP68
Enclosures constructed for indoor or outdoor use; to provide a degree of protection to personnel against incidental contact with the enclosed equipment; to provide a degree of protection against falling dirt; against hose-directed water and the entry of water during occasional prolonged submersion at a limited depth; and that will be undamaged by external formation of ice on the enclosure
6 = Totally protected against entry of dust
8 = Protected against the effects of occasional submersion in water, up to 10 m (33 ft)
12
IP52
Enclosures constructed with knockout(s) for indoor use; to provide a degree of protection to personnel against incidental contact with the enclosed equipment; to provide a degree of protection against falling dirt; against circulating dust, lint, fibers and flyings: and to provide a degree of protection to against dripping and light splashing of liquids
5 = Protected against dust; limited to ingress (no harmful deposit)
2 = Protected against direct sprays of water up to 15° from the vertical
12K
IP52
Enclosures constructed with knockout(s) for indoor use; to provide a degree of protection to personnel against incidental contact with the enclosed equipment; to provide a degree of protection against falling dirt; against circulating dust, lint, fibers and flyings: and to provide a degree of protection to against dripping and light splashing of liquids
5 = Protected against dust; limited to ingress (no harmful deposit)
2 = Protected against direct sprays of water up to 15° from the vertical
13
IP54
IP54 Enclosures constructed for indoor use; to provide a degree of protection to personnel against incidental contact with the enclosed equipment; to provide a degree of protection against falling dirt; against circulating dust, lint, fibers and flyings: and against the spraying, splashing and seepage of water, oil and non-corrosive coolants.
5 = Protected against dust; limited to ingress (no harmful deposit)
4 = Protected against water sprayed from all directions; limited to ingress permitted

BACK TO TOP


DSE HOME | Sealed Monitors | Rugged Computers | OEM Services | Contact Us | RMA Form | Drivers | Installation | Manuals | Warranty | FAQs | Pressroom | About DSE | Site Map
Public Safety | Military | Aerospace | Service and Utilities | Heavy Equipment | Logistics | Food Processing | Pharmaceutical

 

 

DSE HOME